MODEL 7110DR DRAIN ELBOW |
|
|
|
7127 STANDPIPE TEE |
|
|
|
7125 BULLHEAD TEE |
|
|
|
Shurjoint |
|
|
|
ductile iron per ASTM A536 Gr. |
|
|
|
and or ASTM A395 Gr. |
|
|
|
dimensions are manufacturer’s standard. |
|
|
|
Shurjoint standard fitting pressure ratings |
7110DR |
7127 |
7125 |
conform to the ratings of Model 7707 |
|||
couplings. |
|
|
|
For Fire Protection pressure rating, listing, and approval information, refer to Data Sheet
MODEL 7110DR DRAIN ELBOW
The Model 7110DR is a
Full warranty terms can be found on www.shurjoint.com
Model 7110DR Drain Elbow
Nominal |
Pipe |
|
Dimensions |
|
|
|
Pipe Size |
O.D. |
C - E |
D |
E |
Weight |
|
in |
in |
in |
in |
in |
Lbs |
|
mm |
mm |
mm |
mm |
mm |
Kgs |
|
2 |
2.375 |
3.27 |
2.25 |
1.57 |
2.2 |
|
50 |
60.3 |
83 |
57 |
40 |
1.0 |
|
2½ |
2.875 |
3.75 |
2.75 |
1.57 |
2.8 |
|
65 |
73.0 |
95 |
70 |
40 |
1.3 |
|
76.1mm |
3.000 |
3.75 |
2.75 |
1.57 |
2.8 |
|
76.1 |
95 |
70 |
40 |
1.3 |
||
|
||||||
3 |
3.500 |
4.25 |
2.75 |
1.93 |
4.6 |
|
80 |
88.9 |
108 |
70 |
49 |
2.1 |
|
4 |
4.500 |
5.00 |
2.75 |
2.48 |
6.6 |
|
100 |
114.3 |
127 |
70 |
63 |
3.0 |
|
165.1mm |
6.500 |
6.50 |
2.75 |
3.54 |
13.4 |
|
165.1 |
165 |
70 |
90 |
6.1 |
||
|
||||||
6 |
6.625 |
6.50 |
2.75 |
3.54 |
13.4 |
|
150 |
168.3 |
165 |
70 |
90 |
6.1 |
|
8 |
8.625 |
7.76 |
3.27 |
4.49 |
25.6 |
|
200 |
219.1 |
197 |
83 |
114 |
11.6 |
MODEL 7127 STANDPIPE TEE
The Model 7127 is a
|
|
|
|
|
|
Full warranty terms |
|
|
|
|
|
|
|
can be found on |
|
|
|
|
|
|
|
www.shurjoint.com |
|
|
|
Model 7127 Standpipe Tee |
|
|
|
||
Nominal |
Pipe |
|
Dimensions |
|
|
|
|
|
Center to End of Run |
|
Center to End of Branch |
|
|
||
Pipe Size |
O.D. |
|
|
Weight |
|||
|
|
||||||
in |
in |
|
in |
in |
|
Lbs |
|
mm |
mm |
|
mm |
mm |
|
Kgs |
|
4 x 4 x 2½ |
4.500 x 4.500 x 2.875 |
3.25 |
|
4.00 |
5.84 |
||
100 x 100 x 65 |
114.3 x 114.3 x 73.0 |
83 |
|
102 |
2.65 |
||
6 x 6 x 2½ |
6.625 x 6.625 x 2.875 |
3.25 |
|
5.00 |
9.48 |
||
150 x 150 x 65 |
168.3 x 168.3 x 73.0 |
83 |
|
127 |
4.30 |
MODEL 7125 BULLHEAD TEE
The Model 7125 is a
|
|
|
|
|
|
|
|
Full warranty terms |
|
|
|
|
|
|
|
|
|
can be found on |
|
|
|
|
|
|
|
|
|
www.shurjoint.com |
|
|
|
|
|
Model 7125 Bullhead Tee |
|
|
|
||
|
Nominal |
|
Pipe |
|
Dimensions |
|
|
|
|
|
|
|
Center to End of Run |
|
Center to End of Branch |
|
|
||
|
Pipe Size |
|
O.D. |
|
|
Weight |
|||
|
in |
|
in |
|
in |
|
in |
|
Lbs |
|
mm |
|
mm |
|
mm |
|
mm |
|
Kgs |
|
2 x 2 x 2½ |
|
2.375 x 2.375 x 2.875 |
3.74 |
|
3.27 |
4.03 |
||
|
50 x 50 x 65 |
|
60.3 x 60.3 x 73.0 |
95 |
|
83 |
1.83 |
||
|
2 x 2 x 3 |
|
2.375 x 2.375 x 3.500 |
4.25 |
|
3.74 |
4.34 |
||
|
50 x 50 x 80 |
|
60.3 x 60.3 x 88.9 |
108 |
|
95 |
1.97 |
||
|
2 x 2 x 4 |
|
2.375 x 2.375 x 4.500 |
5.00 |
|
4.02 |
7.05 |
||
|
50 x 50 x 100 |
|
60.3 x 60.3 x 114.3 |
127 |
|
102 |
3.20 |
||
|
2½ x 2½ x 3 |
|
2.875 x 2.875 x 3.500 |
4.25 |
|
3.75 |
5.62 |
||
|
65 x 65 x 80 |
|
73.0x 73.0 x 88.9 |
108 |
|
95 |
2.55 |
||
|
2½ x 2½ x 4 |
|
2.875 x 2.875 x 4.500 |
5.00 |
|
4.00 |
7.32 |
||
|
65 x 65 x 100 |
|
73.0 x 73.0 x 114.3 |
127 |
|
102 |
3.32 |
||
|
3 x 3 x 4 |
|
3.500 x 3.500 x 4.500 |
5.00 |
|
4.00 |
7.94 |
||
|
80 x 80 x 100 |
|
88.9 x 88.9 x 114.3 |
127 |
|
102 |
3.60 |
||
|
4 x 4 x 6 |
|
4.500 x 4.500 x 6.625 |
6.50 |
|
5.00 |
14.99 |
||
|
100x 100 x 150 |
|
114.3 x 114.3 x 168.3 |
165 |
|
127 |
6.80 |
||
|
5 x 5 x 8 |
|
5.563 x 5.563 x 8.625 |
7.75 |
|
5.50 |
31.00 |
||
|
125 x 125 x 200 |
|
141.3 x 141.3 x 219.1 |
197 |
|
140 |
14.00 |
||
|
6 x 6 x 8 |
|
6.625 x 6.625 x 8.625 |
7.75 |
|
6.50 |
29.12 |
||
|
150 x 150 x 200 |
|
168.3 x 168.3 x 219.1 |
197 |
|
165 |
13.21 |
MATERIAL SPECIFICATIONS
• Fitting body:
Ductile Iron to ASTM A536, Gr.
• Surface Finish:
Orange color painted or red RAL3000 color painted.
Hot dip galvanized (Option).
Epoxy coated in red RAL3000 or other colors (Option)
General Notes:
Pressure Ratings for fittings conform to the working pressure of the coupling used to join the system.
Listed and or Approved Pressures are pressure ratings for fire protection systems, tested and approved by various approval bodies. Please always refer to the latest approval data posted on the Shurjoint website.
Field Joint Test For one time only the system may be tested hydrostatically at 1½ times the maximum working pressure listed (AWWA C606 5.2.3).
Warning: Piping systems must always be depressurized and drained before attempting disassembly and or removal of any components.
The 10 Year Limited Warranty applies to manufacturing defects only and does not cover severe service/temperature applications or wear parts.
Shurjoint reserves the right to change specifications, designs and or standard without notice and without incurring any obligations.
Job Name: |
System No. |
|
Location: |
Contractor: |
|
Approved: |
Date: |
Engineer: |
|
Approved: |
Date: |
Shurjoint product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Shurjoint Technical Service. Shurjoint reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligations to make such changes and modifications on Shurjoint products previously subsequently sold.
FRASERS Industrial Supply Companies